Build my own cabin - DIY projects

What Size Wire Should I Use?

For residential applications, the most common wire sizes used are 12 gauge and 14 gauge ROMEX.  These wires cover most of your wall outlets and lighting circuits.  You will have a few larger gauge wires for things like your stove, dryer, water heater, or air conditioner.  Wire sizing is very important and something your inspectors should be looking for.  Wire size requirements are specified by the National Electrical Code (NEC) and should not be violated as there safety reasons for the specified sizes.  If in doubt, talk to a licensed electrician or your inspector.

 

The table below specifies the rated amperage for common copper and aluminum wire sizes.  Wires are rated either 60C, 75C, or 90C.  This has to do with how much heat the insulation on the wire is rated to withstand.  The table has columns for copper and aluminum wires.  You'll typically be looking at copper unless you are feeding something like a subpanel where it becomes more cost efficient to run aluminum.  The amperage values in the table are maximums and should not be exceeded.  As a rule of thumb, if your wire runs are over 100ft you should use the next larger size wire to avoid excessive voltage drops.  You should also think about bumping up a size if the cable is in a conduit or grouped with a bunch of other wires in a place where they can't dissipate heat easily.

Ampacities of Insulated Conductors

Size Temperature Rating of Conductor Size
AWG 60ºC 75ºC 90ºC 60ºC 75ºC 90ºC AWG
(140ºF)  (167ºF)  (194ºF)  (140ºF)  (167ºF) (194ºF)
Types Types Types Types Types Types
T
TW
UF
THW
THWN
XHHW
USE
RHH
THHN
XHHW 
T
TW
UF
THW
THWN
XHHW
USE
RHH
THHN
XHHW 
0 Copper Aluminum  
14 20 20 25 ---- ---- ---- ----
12 25 25 30 20 20 25 12
10 30 35 40 25 30 35 10
8 40 50 55 30 40 45 8
6 55 65 75 40 50 60 6
4 70 85 95 55 65 75 4
3 85 100 110 65 75 85 3
2 95 115 130 75 90 100 2
1 110 130 150 85 100 115 1
0 125 150 170 100 120 135 0
00 145 175 195 115 135 150 00
000 165 200 225 130 155 175 000
0000 195 230 260 150 180 205 0000
250 215 255 290 170 205 230 250
300 240 285 320 190 230 255 300
350 260 310 350 210 250 280 350
400 280 335 380 225 270 305 400
500 320 380 430 260 310 350 500

The values in this table come from NEC 2008, table 310-16.  In addition to these requirements, NEC 240.4 specifies overcurrent protection or breakers for some of the common residential sizes as follows:

14 AWG Copper: 15 amperes
12 AWG Copper: 20 amperes
10 AWG Copper: 30 amperes

Where do wire size numbers come from?

Considerations that go into the requirements on wire sizing include voltage drop and heat buildup.  The smaller a given wire is in diameter, the higher its resistance per foot.  See the copper wire resistance table here.  When the resistance is higher, the wire will heat up more, and there will be more voltage drop from one end of wire to the other.  This is why on longer runs you need to consider using a larger gauge wire.  Long runs of wire can create enough voltage drop that your appliances at the end of the line might be given a voltage that is outside of their operating range (ie. 200V on a 240V appliance).  This can damage equipment like motors or compressors that are designed for a specific voltage range.

As a rule of thumb you should target less than 3% voltage drop on a given circuit.  There are some voltage drop calculators here that can help you determine how much voltage drop you'll have with a particular length of wire.

One thing to keep is mind is that you can never go wrong by using a larger wire than is required.  Things can go catastrophically wrong if you use wire that is too small, particularly if paired with breakers sized for a larger gauge wire.

 

Back

Wiring a House