NEC 2014: Table 310.15(B)(2)(a)
Ambient Temperature Correction Factors | ||||
For ambient temps of other than 30C (86F), multiply allowable ampacities shown in ampacity tables by the appropriate factor shown below | ||||
Ambient Temp (C) | Temperature Rating of Conductor | Ambient Temp (F) | ||
60ºC | 75ºC | 90ºC | ||
10 or less | 1.29 | 1.20 | 1.15 | 50 or less |
11-15 | 1.22 | 1.15 | 1.12 | 51-59 |
16-20 | 1.15 | 1.11 | 1.08 | 60-68 |
21-25 | 1.08 | 1.05 | 1.04 | 69-77 |
26-30 | 1.00 | 1.00 | 1.00 | 78-86 |
31-35 | 0.91 | 0.94 | 0.96 | 87-95 |
36-40 | 0.82 | 0.88 | 0.91 | 96-104 |
41-45 | 0.71 | 0.82 | 0.87 | 105-113 |
46-50 | 0.58 | 0.75 | 0.82 | 114-122 |
51-55 | 0.41 | 0.67 | 0.76 | 123-131 |
56-60 | — | 0.58 | 0.71 | 132-140 |
61-65 | — | 0.47 | 0.65 | 141-149 |
66-70 | — | 0.33 | 0.58 | 150-158 |
71-75 | — | — | 0.50 | 159-167 |
76-80 | — | — | 0.41 | 168-176 |
81-85 | — | — | 0.29 | 177-185 |
Click the icons below to get our NEC® compliant Electrical Calc Elite or Electric Toolkit for Android and iOS. The Electrical Calc Elite is designed to solve many of your common code-based electrical calculations like wire sizes, voltage drop, conduit sizing, etc. The Electric Toolkit provides some basic electrical calculations, wiring diagrams (similar to those found on this website), and other electrical reference data.